HVAC Repair in Las Vegas – Soft Start Installation

We installed a 16 amp soft start to help reduce inrush current and improve the performance of the system. Before installation, the inrush current was reading 113 A. After installation, the inrush dropped to 58.8 A. Proper wiring and mounting were verified and secured before completing the job.

See also: AC Blowing Warm Air? A Failed Capacitor on a 5-Year-Old Lennox in Henderson

Close-up of HVAC condenser wiring and new soft start module with secure cable management.

What We Found

The system was drawing 113 amps of inrush current, far exceeding normal startup levels. This can lead to long-term damage on compressors and higher electrical stress. The unit was operating but at a clear disadvantage without soft start protection.

How We Fixed It

We installed a CM870-16A ICM soft start module and securely fastened all associated wiring to the panel. After confirming proper connections, we re-tested the system to verify startup improvements. The job also included a visual inspection of the thermostat and electrical configuration.

How it turned out

With the soft start module installed, inrush current dropped from 113.9A to 58.8A. The unit now starts more smoothly, reducing strain on components and improving long-term reliability. Customer was satisfied and is now protected against future compressor wear.

Safety note: HVAC repairs involve high voltage, refrigerant and, on gas furnaces, combustion gases. Leave them to a licensed technician.