Furnace Only Heating Part of the Day? A Corroded Fuse in This Las Vegas Home

When a furnace heats on and off throughout the day with no clear pattern, a failing electrical connection is a common culprit. On this 8-year-old Rheem furnace with a Honeywell HZ311 zoning board, the fuse on the furnace control board was completely corroded, so the heating circuit kept cutting in and out. Replacing the fuse restored steady heat. We also found the furnace running hot: its temperature rise was 75°F, above its rated 35–65°F range, so we lowered the gas pressure from 3.79 to 3.08 inches of water column, bringing the rise down to a safe 40°F.

Technician using a dual-port manometer to check gas pressure in an HVAC system.

What We Found

  • The furnace heated on and off throughout the day, with no clear pattern.
  • Both thermostats, the Honeywell HZ311 zone board and the damper motors all checked out.
  • We traced the control-board voltage to the fuse: it was completely corroded, so the heating circuit kept cutting in and out.
  • The furnace was also running hot: a 75°F temperature rise against its rated 35–65°F.

How We Fixed It

  • Replaced the corroded fuse on the furnace control board.
  • Lowered the gas pressure from 3.79 to 3.08 inches of water column.
  • Re-measured the temperature rise: 40°F, inside the furnace’s rated range.
  • Ran full heating cycles to confirm steady heat.

How it turned out

The furnace now heats steadily and runs within its rated temperature rise. If the problem ever comes back, the control board itself should be checked.

When to call: if your furnace keeps cutting out, call a technician. An intermittent electrical fault can strand you without heat, and a furnace running above its rated temperature rise is a safety issue. If some rooms stay colder than others, see rooms at different temperatures, or book heating repair. Call (702) 381-5080 →

Questions homeowners ask

Why does my furnace work sometimes and not others?Intermittent heat usually points to a connection that works only part of the time: a corroded fuse or terminal, a loose wire, or a failing control board. On zoned systems a thermostat or zone-board fault can look the same, so a technician should test each step.

Can a corroded fuse cause intermittent heat?Yes. Corrosion can let current through some of the time and block it at other times, so the heating circuit cuts in and out. That’s what happened here.

What is furnace temperature rise, and why does it matter?It’s the difference between the air entering the furnace and the air leaving it. Every furnace has a rated range (35–65°F for this one). Running above it means the furnace is overheating, which wears parts and can be unsafe. We brought this one from 75°F down to 40°F. Another furnace job: a failed hot surface igniter.

Expert insight

“When a furnace cuts in and out with no pattern, don’t assume it’s the thermostat. On zoned systems we test every step from the thermostats down to the control board, and the cause is often something small, like this corroded fuse. We also check the temperature rise, because a furnace running hot wears out early.”
Fred Prandecki, Co-owner at Bob's Repair
Fred PrandeckiCo-owner

Safety note: HVAC repairs involve high voltage, refrigerant and, on gas furnaces, combustion gases. Leave them to a licensed technician.

Team of Bob's Repair technicians in Paradise, NV, performing maintenance on outdoor AC units to extend their lifespan, set against the backdrop of a local home and a palm tree.

Why Bob's Repair

3,000+Google reviews across our offices

Licensed in NevadaNV license 0085640 | 0088730

4 officesacross the Las Vegas valley

Open 7 daysa week

Chat with Bob's Repair