The new pressure switch is in, and the inducer motor, venting and burner flame all checked out.
When to call: if your furnace starts and then shuts off after a short time, or does this several times before giving up, call a technician. The pressure switch is a safety device, so never bypass it. Attic problems can raise your bills too: see hidden attic problems and is your attic wasting money. Call (702) 381-5080 →
Questions homeowners ask
What does a furnace pressure switch do?It’s a safety switch. It confirms the inducer motor is pulling combustion gases out through the vent before the furnace is allowed to light. No draft, no flame.
Why does my furnace start, then shut off after a few seconds?If the pressure switch doesn’t confirm proper draft, the control board stops the startup. A failing switch, a blocked vent or a weak inducer motor can all cause it. A different cause of on-and-off heat: a corroded control board fuse.
Is it the switch or the inducer motor?A technician tests both: whether the inducer pulls proper draft, and whether the switch responds to it. On this job the inducer pulled -0.9 in. w.c., more than the -0.55 in. w.c. the switch needs, and the vent was clear, so the switch itself was at fault.